OPERATING MODE
When you turn on the ECB-001 controller each time, the P.I.D. will be in the OPERATING mode by default. While in the OPERATING MODE, you can press the INDEX button to cycle through the below parameters to verify each one is at the proper setting. Keep scrolling until you return back to the 123.4 parameter (i.e. current set temperature), then stop.
PARAMETER | PROPER SETTING |
123.4 (random example) | Displays the current Set Temperature (SV). |
r – S | r U n |
L o C | oFF |
o U t 1 | Either 100 or 0 |
NOTE 1: If you inadvertently assign the value of LOC 1 or LOC 2 to the LoC parameter, it will lock some or all of the buttons/settings, and you won’t be able to change them until they are unlocked. To unlock them, press the ENTER button and INDEX button simultaneously for 1-2 seconds.
NOTE 2: While in the OPERATING mode, it’s not necessary to press the INDEX button each time before changing the temperature setting. Users can change the temperature setting simply by pressing the ARROW keys, then the ENTER button to lock in that new setting.
REGULATION MODE
While in the OPERATING MODE, press & hold the ENTER button for 1 second to get into the REGULATION mode – then, press the INDEX button then cycle through the parameters to verify each one is at the proper setting. Then, press the ENTER button again to return back to the OPERATING mode.
PARAMETER | PROPER SETTING |
AT | OFF |
P | 24.0 |
I | 340 |
D | 41 |
Cof | 0 |
HLPd | 4 |
tPot | 0.0 |
tP6n | 0.0 |
INITIAL SETTINGS MODE
While in the OPERATING MODE, press & hold the ENTER button for 3-4 seconds to get into the INITIAL SETTINGS mode – then cycle through parameters to verify each one is at the proper setting. Then, press the ENTER button again to return to the OPERATING mode.
PARAMETER | PROPER SETTING |
Inpt | Y2 |
Tpun | F |
tP-H | 600.0 |
tP-L | 50.0 |
Ctrl | PID |
S-HC | HEAT |
ALA1 | 0 |
ALA2 | 0 |
C-SL | ASCII |
CoSH | OFF |
C-no | 1 |
bPS | 9600 |
Len | 7 |
Prty | EVEN |
Stop | 1 |